| Question:
I'm a very keen DIYer - and when I had to replace an unvented hot
water cylinder I actually paid a "professional plumber" company to
install everything.
However, I wasn't actually happy with them (they deliberately made it
a full days work and were very very very slow on basics. LOADS of
visits to van for 20 mins....). They installed the cylinder and
didn't really test the temperature/pressure relief valve in detail as
they never went out the back where the outlet was.... Also - they
left the tank temp on max
That was 3 years ago.When you check the install - the first bend under the tundish is too
close (as per the documented minimum in the manual) and the pipe isn't
perfectly vertical. Anyway - we probably dumped the entire tank (at
least once!) - and fortunately most escaped down the overflow (not
all).
The TPR valve is faulty - leaks on cold water and under no pressure.
ALAS - thats the history - if only we knew a good guy locally :)
So may I ask some questions?
1 - Do I have any comeback on the plumber - or am I likely to be told
its tough luck; out of guarentee period; no proof; no "professional
service"? (I'm not expecting any!)
2 - Do TPR valves fail normally? Should they be replaced regularly?
3 - Where can I get TPR valves from? Its a reliance valve. TPR15.
95mm probe. 7 bar. 90-95'C DN15-DR - 15mm outlet, 1/2" male inlet.
Google hasn't found any supplier
4 - The tank is an Ariston contract cylinder and has ProTech anti-
corrosion system a "magnesium anti-corossion anode". It has a red
error light on - assume annode is duff and may need replacing - though
the troubleshooting guide suggests the PCB is duff. Any thoughts?
Where can I get one from, and is it simply a case of unscrewing the
old anode and putting in new?
Answer:
Doesn't happen quite as you describe. Its not true that the entire tank is
dumped. First thing that happens is that the pressure driven by the
pressure vessel expansion is relived, then the flow continues indefinately
driven by the cold supply. Wondering if another installer shortcoming is
that the probably required pressure regulator on the cold is missing or not
set. Not sure what the setting for the Ariston is but with mine it's 3 bar.
Another possibility which might have triggered the TPR failure is loss of
pressure in the pressure vessel.
I doubt the distance to first bend is critical, the slope and length of
the near horizontal section would govern the discharge. I take it the
discharge pipework is large enough? Should probably be 28mm min.
Bound to say that there are annual checks which you appear to have
overlooked. If you are a competent DIYer I would sort the problems out
myself in accordance with the installation instructions and cite the
original receipts etc as provenence if you come to sell. I think the high
discharge rate may have more to do with the failure mode of the TRV. If so
its bad luck.
More question: cost of a plumberReplace 23 year old galvanized plumbing?Plumbing the BasementAntique toilet seat--won't stay upCouple of plumbing related questionAsk a plumber?Ask EU: Plumber callout chargesPlumbing repair questionplumbing and wiring questionsNEED a plumberPlumbing career?Advice Needed - Commercial Water Product100 gallon water heater choices.Buying plumbing fixtures online?Designer outlet shopping in Ashford - open yet?OT - (sort of)...D I Y Plumbing sites?Plumbing in the tubSecret password for hiring a plumber?Anglian Water Emergency Plumbinggeneral commercial machine plumbing questionPlumbing supplies online/mail order?Plumber issues ... what would be the best way to handle thisgood plumber?WHAT SHOULD A LICENSED PLUMBER MAKEHigher a PLUMBER?tenant, landlord, plumber, burst hot water serviceIs my plumber exagerating?Recommend a solution to this CH problem + need a plumberSaving water with plumbing bypass?PEX plumbing, water softener install, exposed PEX in the closetPlumber Gases OAP!Plumber ripoff?Plumbing ApprenticeshipCareer for a misanthropeplumber cost per day?Plumber billing practicesLandlords plumber damaged furnitureLook out Plumber boy!OT: Plumber's Hourly RateGetting a plumbing licenseWood filler using plumbers puttyGood plumber at reasonable rates in Sth East Melb?Condo plumbing repairhow do you find a good reliable plumber to service your boiler?The 'art' of using a plumbing snake.Port of Tampa?gasline teflon tape for plumbing?advice on plumber toolsNew Home Slab Plumbing CatastropheHard water effects on plumbing and heating systems?Plumbing and Electric Code booksPlumbing codes questionPlumbing inspector nightmareShow I give the plumbing contractor my house key?Plumbing contractor--sumpBAD PLUMBING DESIGNplumbing diagram for house addition..Plumbing diagramsPlumbing emergency -- shower valveAre push fit plumbing fittings any good?
|